FM APPROVED Fuel Tank Polishing Systems

Fuel Technologies International manufactures the most advanced diesel fuel maintenance systems on the market today, providing unmatched equipment quality and customer service. Our systems provide the following:

Affordable system for diesel fuel tank maintenance (Perfect for Fire Pump Applications)

FM APPROVED and NFPA compliant diesel fuel maintenance equipment.

NEMA 3R compliant cabinet with zinc primer and powder coat finish

99% fuel sediment removal for best diesel fuel quality

Nearly 100% water removal

UL Listed Controller

Automatic Fuel Filtration runs on an optimum schedule, with automatic Shut-Off & Alarms for: Water Detection, Filter Saturation, and Leak Detection (Additionally Flow Loss, High Pressure, and Motor Overload depending on Fuel maintenance system selected)

​

In an emergency where a loss of power occurs, mission critical facilities are dependent on the operability and reliability of their emergency power systems for safety, security, and uninterrupted operation.

FTI-1_edited.jpg

FTI-1.5A Fire Pump Fuel Tank Cleaning System

The FTI-1.5A is the optimum fuel maintenance system for Single Tank of 1,000 gallons or less of stored diesel.​

  • FM APPROVED and NFPA compliant diesel fuel maintenance equipment

  • 99% fuel sediment removal for best diesel fuel quality (2 Micron)

  • Designed for rack or wall mount 24"W x 24"H x 9"D

  • Nearly 100% water removal

  • 90 Lbs - Shipping weight

  • UL Listed Controller

 

Automatic Fuel Filtration runs on an optimum schedule, with automatic Shut-Off & Alarms for: Water Detection, Filter Saturation, and Leak Detection

Fire Pump Tank Skid.jpg

Fire Pump Fuel Tank Cleaning

NFPA states that automated systems are acceptable per;
"NFPA 20 - A11.6.4 - Active systems that are permanently added to fuel tanks for removing water and particulates from the fuel can be acceptable, provided the following apply:
1. All connections are made directly to the tank and are not interconnected with the engine or its fuel supply and return piping in any way.
2. There are no valve or other devices added to the engine or its fuel supply and return piping in any way.

fm_approved.png

Why Add A Fuel Polishing System? 

Fire Pumps are run for 30 minutes weekly to assure start-up, but is the fuel in the fuel tank checked at the same time for water and contamination? Probably not. NFPA 25 requires that the fuel storage tank for a Fire Pump be checked & cleaned for free water weekly. An automated stored diesel fuel maintenance system (ADFMS) installed properly will remove near 100% of free water and remove particulate to 2 microns. If you do not clean the tank weekly, it will begin to produce fuel degradation, microbial growth, & sediments.


Fuel Technologies International wants to help after seeing many maintenance companies not providing the NFPA 25 standard - 5-5.1 "Water in system - Check / Clean Weekly". Knowing this, we are providing the most efficient solution to help save lives, & assets.

bottom of page